From data to decisions
Estimate a growth rate and compare three feeding strategies under the same disturbance.
You will be able to
- Align signals and estimate net growth from biomass inventory.
- Decide when feedback has enough evidence to act.
- Connect a monitored process parameter to product quality.
Extract a usable growth signal
Choose a sampling interval short enough to resolve the fastest event of interest. Record the sample timestamp separately from the reporting time. Align signals before calculating ratios. A moving average suppresses noise but rounds transitions. A centred Savitzky–Golay polynomial filter can preserve local slopes but requires future data. A causal implementation trades delay against noise and can overshoot.
Flag an isolated spike with a robust local statistic and retain the raw value. Check a sustained residual against a second probe or assay before declaring drift. A changing process can move both sensors together. A redundant sensor that shares a calibration error offers little protection.
X is concentration and V is volume. In batch with constant V, use the concentration ratio. In fed-batch, include changing volume. Biomass removed by harvest, sampling or death needs its own balance. A longer window reduces sensitivity to endpoint noise and introduces more delay.
Quick check · 2 questions
Feed controller
An open-loop schedule assumes a biomass yield and target growth rate. A DO-stat can respond to a DO rebound after substrate exhaustion when aeration is fixed. A pH-stat can respond to a validated metabolic pH shift. Gas changes, buffering and acid/base addition can mimic either trigger. Use a deadband and maximum dose.

The controller turns a feed profile into pump speed, here an exponential schedule after the batch phase. Measurements such as dissolved oxygen can trigger or trim the feed.
- Feed bottle on its balance
- Feed pump
- Feed line entering the headplate
- Controller showing the feed profile
- Optical DO probe head, the trigger for a DO-stat
OUR feedback relates respiratory demand to substrate uptake. RQ feedback can trim feed when overflow raises CO₂ per mole of O₂ consumed. Capacitance-proportional feeding scales feed to viable biovolume using a calibrated specific uptake. For feedback fundamentals, visit the sister course’s PID control module.
Quick check · 2 questions
PAT basics: connect a signal to quality
Process analytical technology (PAT) uses timely measurements to understand a process and guide decisions that help assure product quality. Start with the product property that matters, then decide what to measure during the run.
A critical quality attribute (CQA) is a property of the material or product that must stay within an appropriate limit or range. For an antibody, one example is its glycan distribution. A critical process parameter (CPP) is an operating variable whose variation affects a CQA. Culture pH may be a CPP if development studies show that it influences that distribution.
A calibrated pH probe lets an operator detect and correct an excursion early. The product assay then checks the glycan distribution. Together, the process trace and the assay help establish how well the control protects the CQA.
Quick check · 2 questions
Estimate a state from noisy measurements
A soft sensor maps observed quantities to hidden states. Metabolic heat needs correction for jacket heat exchange and agitator power. A base-titration estimate needs a stable relationship between neutralising demand and metabolism. Several combinations of states may explain the same measurement: challenge observability across the intended operating range.

The filter blends an exponential growth prediction with noisy measurements. The ribbon is the corrected biomass estimate and the band its uncertainty.
- Corrected biomass estimate
- Noisy measurement
- Uncertainty band around the estimate
- Instruments supplying the measurements
K = P⁻/(P⁻ + R) • x⁺ = x⁻ + K(z − x⁻)
In this lab, x and P are the preceding corrected biomass concentration and variance. Each 0.1 h prediction uses μ = 0.08 h⁻¹, so growth multiplies x by F and variance by F². At time zero the lab starts with an existing prior. Correct each prediction using the innovation z − x⁻ in biomass units. Q is model-error variance per step and R is measurement-error variance, both expressed here in squared biomass units. Large R reduces the correction. The posterior variance is (1 − K)P⁻.
From off-gas to a biomass observation
In the second view convert measured CPR to a biomass observation using CPR/V = (αμ + β)x. Propagate the measurement variance through that conversion. The filter can damp noisy observations, but a drifting coefficient creates systematic error. Without a separate reference it can mistake that error for growth.
Quick check · 2 questions
Hybrid models and advanced control
An extended Kalman filter (EKF) uses local derivatives of nonlinear dynamics. An unscented filter (UKF) propagates weighted sigma points. A Luenberger observer uses a chosen deterministic correction gain. Poor initial states, delayed sensors or incorrect uncertainty can drive either nonlinear filter away from the physical state. Check innovations, nonnegative constraints and independent reference errors.
A published hybrid example combined mass-balance dynamics with a support-vector observation model of cumulative OUR and CPR. Integrals attenuate short noise, but persistent offsets accumulate. Mixing assumptions can fail on scale-up. Hold out complete runs and test a sensor failure before entrusting an actuator to an estimate.
Keep the twin tied to the plant
A digital twin pairs a process model with measurements from the physical process and updates its state or parameters. Define its operating envelope and intended decision. Qualify parameter ranges, sensor delays, model version and fallback. Re-qualify after retraining, scale change or a new medium.
Choose the control law
Model predictive control (MPC) evaluates future actions subject to pump and process constraints, then applies the first action and solves again. A wrong inhibition parameter can drive a simulated controller into starvation. Adaptive control revises parameters or gains as dynamics change. Bound the adaptation and compare against a simple controller on independent disturbances.
Quick check · 2 questions
Sources and further reading
- I. A. Isidro et al., “Online Control Strategies”, Comprehensive Biotechnology, 3rd ed., edited by M. Moo-Young, Elsevier, 2019, ch. 2.64.
- C. Herwig, R. Pörtner and J. Möller (eds.), Digital Twins: Applications to the Design and Optimization of Bioprocesses, Springer, 2021, chs. 3 and 4 by Appl et al. and Yousefi-Darani et al.
- B. Hitzmann (ed.), Bioprocess Monitoring and Control, MDPI, 2020, chapter by Brignoli et al. on specific growth rate control.
- C. Herwig (ed.), Hybrid Modelling and Multi-Parametric Control of Bioprocesses, MDPI, 2018, Simutis and Lübbert, “Hybrid Approach to State Estimation for Bioprocess Control”.
- FDA PAT framework (2004) and ICH Q8(R2), Pharmaceutical Development, on process understanding and critical quality attributes and parameters.
Review and apply
Revisit the opening decision
Module flashcards
Professional review cards
Confidence by objective
Choose low to bring the related cards forward for review.
BioProcess Tools · Module summary
From data to decisions
Key relationships
- μ ≈ ln[(X₂V₂)/(X₁V₁)]/Δt if biomass losses are negligible.
- For exponential growth at fixed μ, Xtotal(t) = Xtotal(0) exp(μt).
Faults and checks
| Observation | Interpretation or check |
|---|---|
| Single isolated spike | Flag it, retain raw data and compare nearby evidence. |
| DO rebounds after a gas change | Check delivery and gas history before acting on a feed trigger. |
Numbers to remember
- If total biomass doubles in 5 h, μ ≈ 0.139 h⁻¹.
- A one-hour result delay belongs to reporting; keep the original sample timestamp.